Campus Residence Fire Event Log for 2011

2018 Report | 2017 Report2016 Report | 2015 Report | 2014 Report | 2013 Report | 2012 Report | 2011 Report | 2010 Report | 2009 Report
Date Time Bldg # Building Name Bldg Type Nature Of Event Device Location Cause
12/22/2011 6:30:00 AM 132 Arbol De La Vida RESIDENTIAL - R2 Nuisance Alarm 'A' Building UAPD attributed the alarm to surging water, same as multiple other alarms
12/16/2011 4:00:00 AM 132 Arbol De La Vida RESIDENTIAL - R2 False Alarm na Repeated water flow issue per UAPD
12/14/2011 2:25:00 AM 85a La Aldea RESIDENTIAL - R2 Nuisance Alarm By 125 Unknown individual pulled pull station, no damages reported
12/13/2011 4:00:00 AM 7/7a Manzanita/Mohave Residence Halls RESIDENTIAL - R2 Nuisance Alarm 3-Mohave Women’s Wing Could not identify the person who pulled it as no witnesses came forward.
12/13/2011 11:20:00 PM 79/79a Huachuca/Kaibab Residence Hall RESIDENTIAL - R2 False Alarm Kitchen Burnt food
12/13/2011 3:50:00 PM 132 Arbol De La Vida RESIDENTIAL - R2 False Alarm Roof Building C, AHU E5 Duct Detector Water damaged duct detector test switch
12/12/2011 3:12:00 PM 132 Arbol De La Vida RESIDENTIAL - R2 False Alarm Roof AHU B6.01 Duct detector Unknown at the time of site investigation
12/10/2011 12:30:00 AM 132 Arbol De La Vida RESIDENTIAL - R2 False Alarm   Loss of water pressure
12/8/2011 5:00:00 PM 151 Babcock RESIDENTIAL - R2 False Alarm Kitchen B101 Burnt food
11/28/2011 2:45:00 PM 131 Likins Hall RESIDENTIAL - R2 Fire 3rd floor Waterflow Someone started a fire to the paper towel dispenser in the mens restroom in room B352 and the sprinkler head released which put the fire out in the restroom. The fire caused significant damage to the wall, floor, and dispenser, and the room is closed down until
11/17/2011 6:45:00 PM 34 Yavapai Residence Hall RESIDENTIAL - R2 False Alarm Room 124, Wing 1E Burnt food
11/16/2011 6:35:00 PM 10 Yuma Residence hall RESIDENTIAL - R2 False Alarm Kitchen Burnt food Officer Kubik provided the following case number: U1111160034
11/14/2011 9:25:00 AM 50/50a Santa Cruz/ Apache Residence Halls RESIDENTIAL - R2 False Alarm Basement Custodial cleaning
11/13/2011 1:30:00 AM 135 Pima Residence Hall RESIDENTIAL - R2 Trouble In room 106b bathroom Strobe in room 106B bathroom going bad
11/5/2011 9:05:00 PM 132 Arbol De La Vida RESIDENTIAL - R2 False Alarm Building B 2nd floor west end of hall near stairs Leaking victaulic inside the wall connected to sprinkler riser
11/3/2011 10:20:00 AM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 False Alarm 6th floor by room 616 The smoke detector was dirty
11/2/2011 10:33:00 AM 122 Posada San Pedro RESIDENTIAL - R2 False Alarm In room 139 The student was heating toast in microwave and it burned setting the alarm off
10/25/2011 5:00:00 PM 10 Yuma Residence hall RESIDENTIAL - R2 False Alarm Kitchen Case #U1110250027 The fire alarm went off due to smoke coming from someone cooking chicken. The person cooking did not turn the hood on over the stove.
10/24/2011 10:20:00 AM 8 Gila Residence Hall RESIDENTIAL - R2 False Alarm Room 200 Burnt food. Students using illegal toaster.
10/22/2011 4:30:00 AM 122 Posada San Pedro RESIDENTIAL - R2 False Alarm   Cause of the alarm was unknown, most likely the disturbed plastic cover
10/21/2011 11:11:00 AM 122 Posada San Pedro RESIDENTIAL - R2 False Alarm SANP 2N Fire alarm in the hallway was dirty which caused the fire panel to sound
10/21/2011 12:25:00 PM 423 Sky View Apartments RESIDENTIAL - R2 False Alarm Not determined UAPD could not determine cause
10/21/2011 4:25:00 AM 423 Sky View Apartments RESIDENTIAL - R2 False Alarm not determined Once again, UAPD could not determine the cause
10/21/2011 7:52:00 PM 423 Sky View Apartments RESIDENTIAL - R2 False Alarm na Other, unknown
10/17/2011 6:40:00 AM 132 Arbol De La Vida RESIDENTIAL - R2 False Alarm Basement Water pressure issue with sprinkler control system in basement
10/13/2011 3:36:00 PM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 False Alarm 6th floor by room 616 Unknown - unable to pin-point cause
10/8/2011 4:00:00 PM 151 Babcock RESIDENTIAL - R2 False Alarm B204 The smoke detector was excessively dirty.
10/7/2011 11:35:00 PM 118 Colonia De La Paz Residence Hall RESIDENTIAL - R2 Trouble 206b Dirty smoke detector
10/1/2011 2:30:00 AM 122 Posada San Pedro RESIDENTIAL - R2 False Alarm Room 390 Burnt Food
9/27/2011 4:50:00 PM 79/79a Huachuca/Kaibab Residence Hall RESIDENTIAL - R2 False Alarm Kitchen Cooking
9/24/2011 10:33:00 PM 423 Sky View Apartments RESIDENTIAL - R2 False Alarm 4th Floor, no specific room Police officers said the alarm was set off on the 4th floor because of burnt food
9/20/2011 9:07:00 PM 31 Cochise Residence Hall RESIDENTIAL - R2 Drill 1st floor lobby Scheduled drill
9/20/2011 9:30:00 PM 34 Yavapai Residence Hall RESIDENTIAL - R2 Drill p/s by 103 Scheduled fire drill.
9/20/2011 6:55:00 PM 52/53 Greenlee/Graham Residence Halls RESIDENTIAL - R2 Drill Greenlee Front Desk Scheduled drill.
9/20/2011 8:28:00 PM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 Drill Lobby Scheduled fire drill
9/20/2011 5:45:00 PM 118 Colonia De La Paz Residence Hall RESIDENTIAL - R2 Drill na Scheduled fire drill
9/20/2011 9:50:00 PM 423 Sky View Apartments RESIDENTIAL - R2 Drill Front lobby area Scheduled fire drill
9/15/2011 7:35:00 PM 5 Coconino Residence Hall RESIDENTIAL - R2 Drill na Scheduled Fire Drill
9/15/2011 8:20:00 PM 8 Gila Residence Hall RESIDENTIAL - R2 Drill Kitchen room 107 Scheduled drill
9/15/2011 8:00:00 PM 10 Yuma Residence hall RESIDENTIAL - R2 Drill Front Desk Scheduled drill with UA Risk Managemnet and ISG
9/15/2011 7:15:00 PM 151 Babcock RESIDENTIAL - R2 Drill By B211A Scheduled fire drill with UA risk management and ISG
9/14/2011 8:00:00 PM 57 Hopi Lodge Residence Hall RESIDENTIAL - R2 Drill Lobby RM&S requested fire drill
9/14/2011 7:30:00 PM 122 Posada San Pedro RESIDENTIAL - R2 Drill Front desk RM&S scheduled fire drill
9/14/2011 8:00:00 PM 123 Pueblo De La Cienega RESIDENTIAL - R2 Drill Front Desk Scheduled Drill
9/6/2011 3:07:00 PM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 False Alarm Fire pump room Arizona side The fire pump pressure switch caused the alarm. The pressure switch was replaced 9/7/11 by residence life.
9/2/2011 2:00:00 AM 151 Babcock RESIDENTIAL - R2 False Alarm D222 Unknown
8/30/2011 1:30:00 PM 7/7a Manzanita/Mohave Residence Halls RESIDENTIAL - R2 False Alarm Mohave basement boiler tanks Res life maint. turned on steam to building without shutdown request, and it set off heat detector
8/27/2011 3:19:00 PM 131 Likins Hall RESIDENTIAL - R2 Trouble Duct detector in room 113 Faulty equipment
8/26/2011 8:30:00 PM 151 Babcock RESIDENTIAL - R2 False Alarm B110 Residents burnt their popcorn in the microwave
8/18/2011 6:19:00 AM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 False Alarm 6th Floor Bathroom Too much hair spray in hallway. Particle detector activated.
8/18/2011 9:10:00 PM 132 Arbol De La Vida RESIDENTIAL - R2 Nuisance Alarm Roof Unclear as to cause of alarm
8/17/2011 7:48:00 AM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 False Alarm By room 421 Strong smell of Perfume \ hairspray in the area / Unknown
8/17/2011 5:40:00 PM 132 Arbol De La Vida RESIDENTIAL - R2 False Alarm Bldg. A, 1st floor TFD said the alarm was caused by a water surge
8/14/2011 10:45:00 AM 122 Posada San Pedro RESIDENTIAL - R2 Trouble Third floor south in room smoke sounder Sounder smoke base in room 391 deffective - removed and replaced sounder smoke base reset FACP - all five in room sounder smoke detectors operational
8/14/2011 2:00:00 PM 131 Likins Hall RESIDENTIAL - R2 Trouble In room A113 duct detector PC board failure
7/30/2011 10:30:00 AM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 False Alarm By room 13 The signal zam circuit was disabled
7/29/2011 10:20:00 PM 132 Arbol De La Vida RESIDENTIAL - R2 False Alarm D Roof Not sure what caused the alarm
7/27/2011 9:15:00 AM 118 Colonia De La Paz Residence Hall RESIDENTIAL - R2 Fire By room S318 The alarm was caused by the light fixture balast that shorted out by room S 318 which set the smoke detector off M5-100. Per Joe, code as fire.
7/14/2011 11:58:00 PM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 Trouble 4th floor by room 420 Smoke sensor
7/6/2011 10:10:00 PM 50/50a Santa Cruz/ Apache Residence Halls RESIDENTIAL - R2 False Alarm Santa Curz lounge 139S Smoke sensor dirty
7/4/2011 11:30:00 PM 10 Yuma Residence hall RESIDENTIAL - R2 Trouble Attic tamper  
7/2/2011 12:50:00 PM 118 Colonia De La Paz Residence Hall RESIDENTIAL - R2 False Alarm 3rd floor by room S-322 Device failure
6/19/2011 8:15:00 PM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 Trouble 8th and 9th floor Unknown
5/19/2011 10:22:00 AM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 False Alarm By room 425 The cause of the alarm was unknown
5/13/2011 5:09:00 AM 122 Posada San Pedro RESIDENTIAL - R2 False Alarm By room 141 Water Leak
5/10/2011 6:21:00 PM 423 Sky View Apartments RESIDENTIAL - R2 False Alarm 218 Burnt plastic in room 218, smoke set off
4/30/2011 8:30:00 AM 57 Hopi Lodge Residence Hall RESIDENTIAL - R2 False Alarm By room 51 Smoke sensor water damage
4/30/2011 9:30:00 AM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 False Alarm 4th floor center hallway Fire extingusher set off by student
4/29/2011 8:30:00 AM 31 Cochise Residence Hall RESIDENTIAL - R2 False Alarm 1st floor 2N2 pull-station/smokes Unknown
4/29/2011 10:10:00 AM 31 Cochise Residence Hall RESIDENTIAL - R2 Trouble Panel N\A
4/28/2011 11:45:00 AM 31 Cochise Residence Hall RESIDENTIAL - R2 Trouble Lobby by front desk Unknown
4/27/2011 10:30:00 AM 31 Cochise Residence Hall RESIDENTIAL - R2 Trouble Panel N/A
4/23/2011 2:35:00 AM 52/53 Greenlee/Graham Residence Halls RESIDENTIAL - R2 False Alarm Greenlee Stairwell 2SW by 219 Intentional
4/22/2011 6:48:00 PM 31 Cochise Residence Hall RESIDENTIAL - R2 Trouble 1W by front desk Unknown
4/19/2011 8:23:00 AM 118 Colonia De La Paz Residence Hall RESIDENTIAL - R2 False Alarm In room 300B The smoke detector was dirty and had to be cleaned
4/17/2011 5:59:00 PM 31 Cochise Residence Hall RESIDENTIAL - R2 False Alarm Lobby na
4/9/2011 10:30:00 PM 121 Villa Del Puente RESIDENTIAL - R2 False Alarm Room 348 Steam from shower
4/6/2011 5:15:00 PM 118 Colonia De La Paz Residence Hall RESIDENTIAL - R2 False Alarm Hall by s-322 UAPD did not indicate cause or location of alarm
3/30/2011 6:20:00 PM 423 Sky View Apartments RESIDENTIAL - R2 False Alarm na Per Leo Taylor, problem was dirty smoke
3/27/2011 9:50:00 AM 31 Cochise Residence Hall RESIDENTIAL - R2 Trouble Lobby Trouble, card 9, power supply/charger, battery charger capacity
3/1/2011 11:30:00 AM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 False Alarm 6th floor Arizona side UAPD accidently set off alarm
2/27/2011 4:17:00 PM 5 Coconino Residence Hall RESIDENTIAL - R2 False Alarm Coconino Kitchen, 1S Pull Station Smoke in kitchen, no known flame. Living Room filled with smoke but cleared out before residents were allowed to return. Pull station in 1S pulled, unknown if the two are related.
2/26/2011 5:59:00 PM 31 Cochise Residence Hall RESIDENTIAL - R2 Fire Third floor alarm was set off Grease fire
2/21/2011 6:10:00 AM 85 Coronado Residence hall RESIDENTIAL - R2 False Alarm By room 404 Device malfunction
2/20/2011 4:40:00 AM 5 Coconino Residence Hall RESIDENTIAL - R2 False Alarm 2nd floor Unknown person pulled the pull station on the second floor, north wing. There was no fire.
2/13/2011 2:06:00 AM 31 Cochise Residence Hall RESIDENTIAL - R2 False Alarm 3rd floor east stairwell The pull station was activated by a student for what appears to be the purpose of doing a prank. There was no fire.
2/8/2011 3:18:00 AM 5 Coconino Residence Hall RESIDENTIAL - R2 False Alarm Elevator Unknown
2/8/2011 11:35:00 AM 85 Coronado Residence hall RESIDENTIAL - R2 False Alarm In room 749 A student burned their noodles in the micowave which caused the alarm
2/5/2011 9:57:00 AM 9 Maricopa Residence Hall RESIDENTIAL - R2 False Alarm na Unknown
2/4/2011 3:16:00 AM 85 Coronado Residence hall RESIDENTIAL - R2 False Alarm 4th Center A resident had discharged the fire extinguisher
1/30/2011 9:50:00 AM 118 Colonia De La Paz Residence Hall RESIDENTIAL - R2 False Alarm S308 Boys D100s pulled “prank” on girls in S308 by expelling the fire extinguisher in the hall.
1/29/2011 1:40:00 AM 31 Cochise Residence Hall RESIDENTIAL - R2 False Alarm Cochise, 2E stairwell Pull-station activated by unknown
1/29/2011 3:30:00 AM 121 Villa Del Puente RESIDENTIAL - R2 False Alarm South Building – 2nd Floor Burnt piece of food from a microwave
1/27/2011 1:45:00 AM 31 Cochise Residence Hall RESIDENTIAL - R2 False Alarm 2E stairwell Someone pulled pull-station on 2E
1/23/2011 8:55:00 PM 34 Yavapai Residence Hall RESIDENTIAL - R2 False Alarm Basement Floor/East Wing Cooking
1/17/2011 11:20:00 PM 34 Yavapai Residence Hall RESIDENTIAL - R2 False Alarm In room smoke detector (Room 13) Student cooking in room
1/14/2011 11:00:00 PM 83/84 Sonora/Arizona Residence Halls RESIDENTIAL - R2 False Alarm 4th floor smokes Student used fire extinghuisher in hallway